Purpose, Function
The generator operates by obtaining drive force from the engine via the drive belt and generates the required electricity for electronic devices.
Construction
The generator is installed on the engine left front side.

Output control is performed by the PCM resulting in the elimination of the IC regulator and the simplification of the construction.
Two delta connection type stator coils have been adopted.


The two stator coils form the circuit having a phase difference, and magnetic pull, which operates between the rotor and stator coil by the phase difference, is theoretically eliminated. Due to this, electromagnetic vibration and generator operation noise (electromagnetic noise) have been reduced.

Pulsation occurring through voltage rectifying using two stator coils having a phase difference is minimized and stable voltage output is supplied.

Operation
For generator control details, refer to CONTROL SYSTEM..
Fail-safe
Function not equipped.
Generator Removal/Installation [Skyactiv G 2.0]
Refrigerant ChargingAnticorrosion, Sound Insulation, And Vibration Insulation
Body Sealing
Apply body sealer where necessary.
For locations where application of body sealer is difficult after installation,
apply it before installation.
Application of Undercoating
Apply an undercoat to the required location of the body.
Application ...
Start Stop Unit
Purpose
Performs control of several systems based on input/output signals from switches.
Function
The start stop unit controls systems based on the input/output signals.
The functions which are controlled are as follows:
Control Table
Control ...
Buckle Switch Inspection
Driver-side
1. Switch the ignition to off.
2. Disconnect the negative battery cable and wait for 1 min or more..
3. Remove the front seat..
4. Remove the front buckle..
5. Inspect for continuity between the buckle switch terminals using a tester.
If not as indicated in the tab ...